Everybody? Welcome to another episode of Let's

2
00:00:37,439 --> 00:00:42,479
Ask Paul, the podcast where you
get to submit questions to me on the

3
00:00:42,640 --> 00:00:49,399
National Electric Code all through our free
portal sponsored by Wicks over at Paul Abernathy

4
00:00:49,799 --> 00:00:54,200
dot com. Now in that portal
you can put your name, email address,

5
00:00:54,240 --> 00:00:58,880
and post your question easy peasy.
You can even listen to all of

6
00:00:58,920 --> 00:01:03,159
the episodes from the Ask Paul series
there as well on that web page.

7
00:01:03,679 --> 00:01:07,560
But that's where you go to submit
questions to me, and if selected,

8
00:01:07,560 --> 00:01:12,239
I'll answer them in an email or
an upcoming podcast much like today's and coming

9
00:01:12,359 --> 00:01:17,840
up starting June twenty eighth, twenty
twenty three. So depending on when you're

10
00:01:17,840 --> 00:01:22,719
listening to this podcast, you can
join us on Wednesday nights at fast Tracks

11
00:01:22,799 --> 00:01:26,079
Live and it's available on all of
our social media platforms, which you can

12
00:01:26,120 --> 00:01:32,000
also watch it free over on fast
tracks Tube as well, even Rumble.

13
00:01:32,079 --> 00:01:34,640
If you want to watch it over
and Rumble, just search for us master

14
00:01:34,719 --> 00:01:38,519
the Anc as our user name everywhere. And we're going to even answer some

15
00:01:38,599 --> 00:01:44,079
of these questions live on air.
So if you want to get your questions

16
00:01:44,239 --> 00:01:48,879
answered live, then submit them to
us through the Paul Abernathy dot com portal

17
00:01:49,280 --> 00:01:56,519
or you could even send them to
support Suppo RT at fast tracks system dot

18
00:01:56,519 --> 00:02:00,599
com and be more than happy to
answer those questions for you during our Wednesday

19
00:02:00,680 --> 00:02:06,799
night show. All Right, so
this question was submitted to me, and

20
00:02:06,840 --> 00:02:10,479
I thought it'd be a great question
to focus on for this episode because there

21
00:02:10,599 --> 00:02:16,719
is a lot of opinions rolling around
about it and misconceptions about conductors and reidentifying

22
00:02:16,719 --> 00:02:21,560
a conductor, and so this is
a very specific question. I've looked it

23
00:02:21,680 --> 00:02:29,039
over and the question is very much
focused on they have some cable that has

24
00:02:29,280 --> 00:02:32,000
a black red blue in it,
and they want they're in a building and

25
00:02:32,120 --> 00:02:38,159
this building hash and these are big
branch circuits by the way, and they

26
00:02:38,240 --> 00:02:44,080
have black red blues and they and
they have another voltage system in the building.

27
00:02:44,240 --> 00:02:46,800
Okay, they have another voltage system
and they want to be able to

28
00:02:46,879 --> 00:02:51,599
use that same cable with black red
blue. But they want to phase it

29
00:02:51,639 --> 00:02:58,120
out brown orange, yellow or whatever
you know, other coloring they want to

30
00:02:58,199 --> 00:02:59,919
use. They want to phase it
out, but they want to use this

31
00:03:00,080 --> 00:03:02,000
same cable. So there's many people
that say that you can't do that.

32
00:03:02,080 --> 00:03:07,400
So let's read us questions, says
Dear Paul, Thanks advanced for your podcasts.

33
00:03:07,520 --> 00:03:10,000
I listened to it every day on
the job site. You have over

34
00:03:10,039 --> 00:03:13,800
six hundred of them. I appreciate
the effort that you put in to help

35
00:03:13,919 --> 00:03:19,280
educate us electricians. My question revolves
around the fact that we purchased quite a

36
00:03:19,360 --> 00:03:25,280
large amount of a metal clad cable
with black red blue inners. We now

37
00:03:25,319 --> 00:03:30,560
have a project where we have two
voltage classes that are on the project,

38
00:03:30,360 --> 00:03:36,919
and our inspector is telling us that
we can't use the black red blue for

39
00:03:37,080 --> 00:03:43,120
the higher voltage classes, which we
typically would mark brown orange yellow. Is

40
00:03:43,159 --> 00:03:46,639
this in the code and why can't
we use this same cable assembly as long

41
00:03:46,680 --> 00:03:51,840
as we reidentified. Thanks in advance
and again, love your podcast. Look

42
00:03:51,879 --> 00:03:55,560
forward to listening to this episode.
Okay, great question. I don't know

43
00:03:55,560 --> 00:03:59,439
how you knew it would become an
episode because I could have just responded back

44
00:03:59,479 --> 00:04:02,800
in an email, which I actually
have, but you it's a great topic,

45
00:04:03,280 --> 00:04:06,879
so I wanted to make sure that
I do a podcast on it.

46
00:04:08,759 --> 00:04:15,360
So what your inspectors saying here is
he's basically invoking the requirements and since you

47
00:04:15,439 --> 00:04:17,439
said it was brand circuits, but
again, there's a feeder rule for this

48
00:04:17,519 --> 00:04:24,800
as well. It's two ten dot
five C and it's the identification of the

49
00:04:24,920 --> 00:04:30,160
ungrounded conductors. Now, in this
scenario, what you've got is you have

50
00:04:30,360 --> 00:04:35,720
a brand circuit that's applying of some
circuits in a building in the premise wiring,

51
00:04:36,120 --> 00:04:42,240
and there's more than one voltage class
in this building. So the rules

52
00:04:42,439 --> 00:04:46,839
calls for the identification of these ungrounded
conductors. So it's not confusing, right,

53
00:04:46,879 --> 00:04:50,439
We know that this black red blues
for one voltage class for one specific

54
00:04:50,480 --> 00:04:55,639
application, and then you have another
one which could be brown, orange,

55
00:04:55,720 --> 00:05:00,519
yellow, but it could be whatever
colors you want generally speak, and we're

56
00:05:00,519 --> 00:05:03,079
not talking about a delta high lag
where it's got to be orange. If

57
00:05:03,199 --> 00:05:08,240
color is a choice, then it
would have to be orange if it's colors

58
00:05:08,319 --> 00:05:10,920
used, because you could use tagging
and other things that not have to be

59
00:05:10,920 --> 00:05:13,319
orange. But that's not what we're
talking about. We're just talking about the

60
00:05:13,360 --> 00:05:17,160
selection of phase colors. And for
those say, oh but it is very

61
00:05:17,199 --> 00:05:21,079
GERMANE, well okay, well then
you go you go read that rule and

62
00:05:21,120 --> 00:05:24,360
you know when it's got to be
orange, then you're happy. You know

63
00:05:24,399 --> 00:05:27,120
when it's got to be orange.
All right, We're not getting into that,

64
00:05:27,240 --> 00:05:30,000
all right, So let me read
what it says. So two ten

65
00:05:30,079 --> 00:05:36,040
dot five identification of brand circuits.
See, it says identification of ungrounded conductors.

66
00:05:36,160 --> 00:05:42,040
And obviously we have two ten dot
five A and B, which is

67
00:05:42,240 --> 00:05:45,439
identification of the grounded conductor, which
is going to send you to two hundred

68
00:05:45,439 --> 00:05:47,279
dot six, and then equipment grounded
conductor which is going to send you to

69
00:05:47,279 --> 00:05:50,959
two fifty dot one nineteen. So
those are covered. So they're really focused

70
00:05:51,120 --> 00:05:56,879
on the ungrounded hot conductors. So
here's what the code says. It says,

71
00:05:57,240 --> 00:06:02,560
ungrounded conductors shall be identified in accordance
with two ten five C one or

72
00:06:03,240 --> 00:06:12,120
two as applicable. Okay, So
C one says this brand circuit supplying from

73
00:06:12,279 --> 00:06:16,680
supplied from more than one nominal voltage
source. It says, where the premise

74
00:06:16,759 --> 00:06:23,879
wiring system has brand circuits supplied from
more than one nominal voltage system obviously in

75
00:06:23,920 --> 00:06:26,480
the building, so you could have
a one twenty two footy volte system in

76
00:06:26,519 --> 00:06:29,000
there, and you could have a
two seventy seven four eighty volt system in

77
00:06:29,040 --> 00:06:32,360
there. Okay, you could have
brand circuits in this building coming from two

78
00:06:32,399 --> 00:06:36,399
separate sources. And again the code
is going to have applications where it permits

79
00:06:36,439 --> 00:06:42,639
you to have these different sources there, or could be a transformer that changes

80
00:06:42,639 --> 00:06:46,839
these sources to different voltage classes within
the building. The point being is you've

81
00:06:46,839 --> 00:06:50,879
got two different voltage classes in here. Okay. It says each ungrounded conductor

82
00:06:51,079 --> 00:07:00,680
of a brand circuit shall be identified
by phase or line and by no voltage

83
00:07:00,720 --> 00:07:08,800
system at all terminations connection splice points
in accordance with two ten two ten dot

84
00:07:08,800 --> 00:07:14,639
five C one A and C one
B, which we're going to look at

85
00:07:14,680 --> 00:07:17,800
here in a second. It says
different systems within the same premise that have

86
00:07:17,959 --> 00:07:24,879
the same nominal voltage should be permitted
to use the same identification. And what

87
00:07:24,920 --> 00:07:28,439
that means is if I have a
one twenty two forty and a one twenty

88
00:07:28,439 --> 00:07:31,120
two aweight in a building, whatever
I use for the one twenty it can

89
00:07:31,160 --> 00:07:34,399
be the same identification, whether it's
the one twenty two forty or the one

90
00:07:34,439 --> 00:07:36,680
twenty two O eight. That's what
that means. Okay, you don't have

91
00:07:36,680 --> 00:07:41,560
to come up with another color just
because of the one twenty volte circuits.

92
00:07:41,759 --> 00:07:44,439
If it's one twenty vold, it's
one twenty volts, so it doesn't matter.

93
00:07:44,720 --> 00:07:46,879
That's what that line says, and
that was actually added last cycle.

94
00:07:47,160 --> 00:07:51,480
Okay, all right, so when
I'm looking at it, and i'm again,

95
00:07:51,560 --> 00:07:56,040
folks, I'm in the twenty twenty
three case. You're wondering, I'm

96
00:07:56,160 --> 00:07:59,319
in the twenty twenty three edition.
But it's the same thing. It really

97
00:07:59,399 --> 00:08:01,920
much pretty much says the same thing
in either one. All right, Now

98
00:08:01,920 --> 00:08:05,879
there's an A and a B.
Here's what A says means of identification.

99
00:08:07,079 --> 00:08:11,959
It says the means of identification shall
be permitted to be by separate color coding,

100
00:08:13,720 --> 00:08:20,519
marking tape, tagging, or other
approved means. Okay, so let

101
00:08:20,600 --> 00:08:24,120
me start out with this. If
you have an MC cable that has black,

102
00:08:24,160 --> 00:08:28,040
red, blue, but you need
to reidentify it for a color scheme

103
00:08:28,120 --> 00:08:33,879
that references another nominal vaultage system,
then you can do that with marking tape.

104
00:08:33,039 --> 00:08:37,360
You could do that with tagging or
other approved means, maybe heat shrink

105
00:08:37,440 --> 00:08:41,519
if that's what the hj's okay with. Maybe you don't want to use the

106
00:08:41,519 --> 00:08:46,159
color coding of the insulation. But
at terminals, remember you're supposed to do

107
00:08:46,240 --> 00:08:52,360
this, where at terminations, connections
and splice points, you're going to reidentify

108
00:08:52,440 --> 00:08:56,759
it with marking tape with the new
color identification that you choose for that voltage

109
00:08:56,799 --> 00:09:03,480
class at that location. So if
that means that I have a red conductor

110
00:09:03,000 --> 00:09:11,080
and I'm wrapping it with brown tape
at the termination, then so be it.

111
00:09:11,879 --> 00:09:16,080
Now the key is I have to
go to B, which is posting

112
00:09:16,240 --> 00:09:20,559
of identification meanings. So if I'm
going to take a conductor that is red

113
00:09:20,600 --> 00:09:24,799
and I'm going to put brown tape
around at the termination, then I need

114
00:09:24,879 --> 00:09:31,000
to make sure that my method of
identifying this is available, okay, And

115
00:09:31,080 --> 00:09:35,080
so let me read you what it
says about posting of identification means. And

116
00:09:35,120 --> 00:09:37,600
remember this is kind of no different
than striping. If I have a certain

117
00:09:37,639 --> 00:09:41,399
color with a certain color stripe on
it, then you identify it accordingly.

118
00:09:41,600 --> 00:09:46,320
This is no different if a red
conductor with brown tape, Okay, however

119
00:09:46,360 --> 00:09:50,759
you identify it to make it very
clear. Then you want to make sure

120
00:09:50,799 --> 00:09:54,360
that you convey that to people.
So here's what it says for B of

121
00:09:54,399 --> 00:09:58,840
this rule. It says posting of
identification means. It says the method you

122
00:09:58,960 --> 00:10:05,120
used, the method you used for
conductors originating within each brand circuit panelboard or

123
00:10:05,559 --> 00:10:11,919
similar brand circuit distribution equipment. Shall
be documented in a manner that is readily

124
00:10:11,919 --> 00:10:20,399
available or shall be permanently posted at
each brand circuit panelboard or similar brand circuit

125
00:10:20,440 --> 00:10:26,120
distribution equipment. The labels shall be
of sufficient durability to withstand the environmental environment

126
00:10:26,200 --> 00:10:33,000
involved, and shall not be handwritten. So you're you're gonna type out this,

127
00:10:33,120 --> 00:10:37,679
you're a phonomic label or whatever you're
going to do in order to make

128
00:10:37,720 --> 00:10:41,559
sure that you have this identification,
okay, And the point of that is

129
00:10:41,600 --> 00:10:46,519
that whatever you choose to do,
whatever you choose to reidentify, wrap and

130
00:10:46,600 --> 00:10:52,360
tape that whoever's there can read it. It's not handwritten. It's very clear

131
00:10:52,840 --> 00:10:56,639
what you're trying to do. So
there's nothing in the code that says that

132
00:10:56,679 --> 00:11:01,799
I can't take a cable with black, red, blue and use it by

133
00:11:01,879 --> 00:11:07,759
reidentifying it, by taping it another
color and making sure that it's very distinctly

134
00:11:07,840 --> 00:11:13,080
marked at these locations. The difference
between the two systems, so what are

135
00:11:13,120 --> 00:11:16,279
the color schemes being used for the
one voltage class and then what's the color

136
00:11:16,320 --> 00:11:22,000
schemes and very distinctive identification of the
other voltage class that will be in the

137
00:11:22,000 --> 00:11:26,320
same building. That are brand circuits
now this also applies to feeders as well.

138
00:11:26,840 --> 00:11:31,519
Okay, same scenario. So I
think it's very clear to me anyway

139
00:11:31,679 --> 00:11:37,120
that it's telling me that I can
do it by color coding, marking,

140
00:11:37,159 --> 00:11:43,480
tape, tags, or other approved
means. And just because my color has

141
00:11:43,480 --> 00:11:48,039
an installation. Remember years ago all
we had was black and we had to

142
00:11:48,080 --> 00:11:50,759
phase these things out. Well,
now just because the installation is colored,

143
00:11:50,759 --> 00:11:54,279
that makes it more convenient to leave. If that's what you want to select

144
00:11:54,360 --> 00:12:00,559
your purchase and get your color coordinated
ahead of time, that's great. But

145
00:12:00,639 --> 00:12:03,279
there's nothing in here that says that
I cannot take a red and put blue

146
00:12:03,279 --> 00:12:07,519
tape on it, or a blue
and put red tape on it, or

147
00:12:07,559 --> 00:12:11,320
a black and put orange tape on
it. There's nothing that says that I

148
00:12:11,360 --> 00:12:18,080
can't do that within the allowance of
two ten five C one right. So

149
00:12:18,320 --> 00:12:22,000
again that's kind of hopefully that answers
the questions. So again, if you

150
00:12:22,080 --> 00:12:26,879
have an inspector who has a problem
with this, you know, again,

151
00:12:26,279 --> 00:12:28,240
if it's in a race way,
you're not going to see it anyway.

152
00:12:28,320 --> 00:12:31,039
The portion that comes out now,
this only requires that you identify it at

153
00:12:31,080 --> 00:12:35,159
the termination, right, and at
any connection point or any splice point that

154
00:12:35,279 --> 00:12:39,000
you maintain it. If you do
it at the panel, you want to

155
00:12:39,000 --> 00:12:41,559
make sure you maintain it through the
system, so no matter where they open

156
00:12:41,639 --> 00:12:45,679
it up, they're very clear what's
going on. Right. But if you

157
00:12:45,720 --> 00:12:48,639
do that, absolutely nothing says that
you can't do that. Now, that

158
00:12:48,679 --> 00:12:52,679
doesn't mean everybody go out and just
buy one standard black red blue and use

159
00:12:52,759 --> 00:12:58,039
that for both one twenty two forty
or one twenty two eight and then use

160
00:12:58,080 --> 00:13:03,960
it again into seventy seven for eighty
although you can. Most people are going

161
00:13:03,000 --> 00:13:07,320
to buy color. That's the whole
purpose of buying. If if you're not

162
00:13:07,360 --> 00:13:09,480
going to do that, then you
might as well just buy black conductors.

163
00:13:09,159 --> 00:13:13,320
Okay, So that's the reason why
people. But in case somebody happen to

164
00:13:13,000 --> 00:13:16,919
run into a situation where they're like, crap, I'm in a bind and

165
00:13:16,960 --> 00:13:20,440
all I have is black red blue
in the SMC cable or for example,

166
00:13:20,919 --> 00:13:26,639
can I reidentify those conductors with phase
tape and the marking tape? And the

167
00:13:26,679 --> 00:13:31,000
answer is absolutely yes. Two ten
dot five C one says it. Now,

168
00:13:31,000 --> 00:13:33,720
whether somebody says, well that's confusing
because I see the insulation color and

169
00:13:33,720 --> 00:13:37,559
I see the tape. Well,
that's because the National Electric Code is not

170
00:13:37,679 --> 00:13:41,799
for the untrained person. If you're
a trained person, then you know what

171
00:13:41,879 --> 00:13:46,159
two ten five C says, and
you're looking at that termination, and you're

172
00:13:46,200 --> 00:13:52,080
looking for the color that's being used
at that termination and how it corresponds with

173
00:13:52,120 --> 00:13:58,240
the required posting of the markings,
right, and then it should be fairly

174
00:13:58,440 --> 00:14:03,360
obvious to you as a trained professional. Okay, we don't want everyday Joe

175
00:14:03,519 --> 00:14:07,279
just doing this. These are trained
professionals and the code is written in a

176
00:14:07,360 --> 00:14:11,240
certain way. So again that's the
importance of learning the code, because if

177
00:14:11,240 --> 00:14:13,919
you don't know the code, then
yeah, I can see where you get

178
00:14:13,919 --> 00:14:18,240
confused. Right. Anyway, that's
my take on it. I hope you

179
00:14:18,320 --> 00:14:20,840
got something out of that and we're
able to help you out just a little

180
00:14:20,879 --> 00:14:24,679
bit. If you have any questions, feel free. I'm more than happy

181
00:14:24,679 --> 00:14:28,360
to give my opinion. Just go
to Paul Abernathy dot com, submit your

182
00:14:28,440 --> 00:14:31,799
question and I will answer it.
Hopefully it'll be answered in the live shows

183
00:14:31,840 --> 00:14:35,360
starting June twenty eighth, but it
also could be on upcoming podcast. Till

184
00:14:35,440 --> 00:15:05,519
next time, Stay safe, God
bless, Ask open